8.28 Burner control
Prepurge time
(9500)
Pre-purging time.
Note: This parameter must only be changed by a heating specialist!
Nominal output prepurging
(9504)
Nominal output fan speed during pre-purging.
Nominal output ignition load
(9512)
Nominal output fan speed during ignition.
Nominal output Partial load
(9524)
Nominal output fan speed under boiler in Low Fire.
Note: If you change this value, please note that prog. no. 2452 is always set high-
er!
Nominal output Full load
(9529)
Nominal output fan speed under boiler in High Fire.
Postpurge time
(9540)
Post-purging time.
Note: This parameter must only be changed by a heating specialist!
Fan output/speed slope
(9626)
Fan output/speed Y-section
(9627)
With this parameter the rotational speed of the fan can be adjusted (e.g. for com-
plex exhaust systems or the conversion of gas condensing boilers for operating
with liquid gas.
- Prog. no. 9626 equates to the incline of the fan characteristic curve
- Prog. no. 9627 equates to the shift of the fan characteristic curve in Y-direction
8.29 Info Option
Display of different information values which depend on the current operation
state. Furthermore, information about the different states are displayed (see sec-
tion State).
Programming
118 Paramount three 30-115 kW 396532 07.11