Legionella funct time
(1644)
Setting the start time for the legionella function. The legionella function will be
carried out at the first release of the DHW preparation with the setting "---".
Legionella funct setpoint
(1645)
Setting the temperature setpoint for killing the germs.
Legionella funct duration
(1646)
With this function, the time will be set, during which the legionella function set-
point is activated to kill germs.
If the colder storage temperature rises above the legionella function setpoint by -1
K, the legionella function setpoint is assumed as met and the timer starts running.
If the storage temperature drops by more than the switching difference +2 K be-
low the required legionella function setpoint, the duration has to be met again. If
no duration has been set, the legionella function has been met immediately on
reaching the legionella function setpoint.
Legionella function circ pump
(1647)
- On: The circulation pump will be switched on in case of active legionella func-
tion.
Caution! There exists a hazard of scalding at the legionella function is activatted.
Circulating pump release
(1660)
- Time program 3: The circulation pump is released, depending on the time pro-
gramme 3 (see prog.no. 540 to 556).
- DHW release: The circulation pump will be released, when the domestic hot wa-
ter preparation has been released.
- Time program4: The circulation pump will be released, depending on the time
programme 4 of the local controller.
Circulating pump cycling
(1661)
The circulating pump will be switched on for 10 minutes and off for 20 minutes
within the release time.
Circulation setpoint
(1663)
In case of undercutting the circulation setpoint (Standard value: 45°C), the circu-
lation pump will be switched on for 10 minutes within the release time. When
reaching the circulation setpoint, but at the earliest 10 minutes later, the pump is
switched off. For this function, the connection of a sensor in the circulation return
is necessary (inputs BX, program no. 5930-5933).
Optg mode changeover
(1680)
Using external switching above the entrances H1-H5 it can be selected into which
operating mode is switched into.
- None: the function is switched off.
8.12 Consumer circuits/
Swimming pool circuit
Flow temp setp cons request
(1859, 1909, 1959)
Setting of the flow setpoint is done with this function, which is effective during
active request of the consumer circuit.
DHW charging priority
(1874, 1924, 1974)
Setting if the connected consumer circuit pump should be used with priority for
domestic hot water charging.
Programming
84 Paramount three 30-115 kW 396532 07.11