
Function Prog.
no.
Level
1)
Standard value
Fan output/speed increase 9626 F 30: 214.3
40: 150.0
60: 98.9
80: 70.5
95: 65.0
115: 58.3
Fan output/speed Y-section 9627 F 30: 100.0
40: 100.0
60: 70.0
80: -30.0
95: 150.0
115: 140.0
*)
kW-settings are approximate values. Exact values can for example are determined by the gas meter.
Info Option
The display of the information values depends on the operation status!
Fault message
Servicing message
Setpoint manual control
Controller stop nominal value
Boiler temperature
State heating circuit 1
State heating circuit 2
State heating circuit 3
State domestic hot water
State boiler
State solar
State solid fuel boiler
State buffer
State swimming pool
Year
Date
Time
Telephone customer service
1)
Eu = End user; C = Commissioning; E = Engineer
Note: Parameters with the program numbers 1- 54 are individual parameters of
the operating unit and the room unit and may, therefore, be set differently on
both devices. All paramteres from programme number 500 onwards are stored on
the controller and, therefore, identical. The value changed last is the valid value.
8.4 Explanations for setting
table
In the following the individual parameters of the Paramount three will be descri-
bed.
Programming
396532 07.11 Paramount three 30-115 kW 69
Commentaires sur ces manuels