Baxi Fires Division 347 Manuel de service Page 91

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 136
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 90
Fig. 22: charging control /schematically)
Tco l
Tem p diff on
Tem p diff off
Tcm in
On
Off
TSt
ON / OFF Collector pump
Tkol Collector temp
TLmin Charging temp min buffer / swimming pool
TSp Storage temperature
Charg temp min DHW st tank
(3812)
In addition to the temperature difference, reaching a certain collector tempera-
ture is necessary for the storage charging process.
Fig. 23: Charging controller (dT)
Tco l
On
Off
SdOn
SdOff
Tcol
On/Off
SdON
SdOFF
Collector temperature
Charging ON / OFF
Temp diff ON
Temp diff OFF
Temp diff ON buffer
(3813)
Temp diff OFF buffer
(3814)
Charging temp min buffer
(3815)
The switching-on and switching-off point of the collector pump is set with these
functions. Basis is the temperature difference between collector temperature and
storage temperature of the buffer.
In addition to the temperature difference, reaching a certain minimum collector
temperature is necessary for the buffer storage charging process.
Temp diff ON swi pool
(3816)
Temp diff OFF swi pool
(3817)
For exceeding or not reaching the difference between solar collector temperature
and swimming pool temperature, the solar pump is switched on and off.
Programming
396532 07.11 Paramount three 30-115 kW 91
Vue de la page 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 135 136

Commentaires sur ces manuels

Pas de commentaire