Function Prog.
no.
Level
1)
Standard value
Flow setp compensation Tv 5145 E 30 s
Full charging with B36
No |Yes
5146 E No
Min start temp diff Q33 5148 E -3°C
Excess interm circ temp del 5151 E 30 s
Configuration
Heating circuit 1
Off | On
5710 C ON
Heating circuit 2
Off | On
5715 C Off
Heating circuit 3
Off | On
5721 C Off
DHW sensor
DHW sensor B3 | Thermostat
5730 E DHW sensor B3
DHW controlling element Q3
No charging request | Charging pump | Diverting valve
5731 F Charging pump
Basic pos DHW div
Last request | Heating circuit | DHW
5734 E Heating circuit
DHW separate circuit
Off | On
5736 E Off
Contact type DHW div valve
Position on DHW | Position on HC
5737 E Position on DHW
Ctrl boiler pump/DHW valve
All requests | Request HC1/DHW only
5774 E All requests
Solar controlling element
Charging pump | Diverting valve
5840 E Charging pump
External solar exchanger
Commonly | DHW storage tank | Buffer storage tank
5841 E Commonly
Combi storage tank
No |Yes
5870 E No
Relay output QX1
None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump
Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 |
Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System
pump Q14 | Heat gen shutoff valve Y4 | Solid fuel boiler pump Q10 |
Time program 5 K13 | Buffer return valve Y15 | Solar pump ext exch
K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18 | Swim-
ming pool pump Q19 | Cascade pump Q25 | St tank transfer pump
Q11 | DHW mixing pump Q35 | DHW interm circ pump Q33 | Heat re-
quest K27 | Heat circuit pump HC1 Q2 | Heat circuit pump HC2 Q6 |
DHW ctrl elem Q3 | Status output K35 | Status information K36 | Flue
gas damper K37 | Fan shutdown K38
5890 C Alarm output K10
Relay output QX2
Parameters see Relay output QX1 (prog.-no. 5890)!
5891 C Heat circuit pump HC1
Q2
Relay output QX3
Parameters see Relay output QX1 (prog.-no. 5890)!
5892 C DHW controlling element
Q3
Programming
58 Paramount three 30-115 kW 396532 07.11
Vue de la page 57